Low temperature rise
More contact plate designs ensure lower product temperature rise.
| Rated current In(A) | 1000A, 1250A, 1600A, 2000A, 2500A, 2900A, 3200A, 3600A, 4000A |
| Rated working voltage Ue(V) 50Hz/60Hz | AC400, AC690, AC800, AC1140, AC1250, AC1500 |
| Rated insulation voltage Ui(V) | 1800V |
| Rated impulse withstand voltage Uimp(kV) | 18kV |
| Power frequency withstand voltage U(V) 1min | AC5000V 50Hz/60Hz |
| Number of poles | 3P, 4P |
| N-pole rated current | 100%In |
| Breaking capacity code | H, HU, HV |
| Rated limit short-circuit breaking capacity (effective value) Icu(kA) | AC400: 100kA AC690: 85kA AC800: 80kA AC1140: 75kA AC1250: 66kA AC1500: 50kA |
| Rated operating short-circuit breaking capacity (effective value) Ics(kA) | AC400: 100kA AC690: 85kA AC800: 80kA AC1140: 75kA AC1250: 66kA AC1500: 50kA |
| Rated short circuit making capacity (peak value) Icm(kA) | AC400: 220kA AC690: 187kA AC800: 176kA AC1140: 165kA AC1250: 145kA AC1500: 105kA |
| Rated short-time withstand current (effective value) Icw(kA) 1s | AC400: 100kA AC690: 85kA AC800: 80kA AC1140: 75kA AC1250: 66kA AC1500: 50kA |
| Rated conditional short-circuit current Icc(kA) | AC400: 100kA AC690: 85kA AC800: 80kA AC1140: 75kA AC1250: 66kA AC1500: 50kA |
| Full break time (no additional delay) (ms) | 12(ms)~18(ms) |
| Closing time (ms) | ≤60(ms) |
| Operating performance(Mechanical life (times); Without maintenance) | 10000(times) |
| Operating performance(Mechanical life (times); Maintenance) | 20000(times) |
| Operational condition(Utilization category) | B |
| Operational condition(Pollution degree) | 3 |
| Operational condition(Ambient grade) | IP40 |
| Operational condition(Ambient temperature) | ≥-40℃ |
| Operational condition(Altitude) | ≤5000m |
| Outline dimension (mm) (H × W × D) (Drawout type 3P) | 430(mm) × 407(mm) × 395(mm) |
| Outline dimension (mm) (H × W × D) (Drawout type 4P) | 430(mm) × 522(mm) × 395(mm) |
| Outline dimension (mm) (H × W × D) (Fixed type 3P) | 390(mm) × 422(mm) × 297.5(mm) |
| Outline dimension (mm) (H × W × D) (Fixed type 4P) | 390(mm) × 537(mm) × 297.5(mm) |
Tips: For more information, please refer to the user manual or specification sheet in the following documentation.
More contact plate designs ensure lower product temperature rise.
Large opening contact, new staggered boosting structure, new gas production material, efficient arc extinguishing.
Professional testing for high and low temperature, high altitude, high tide and humidity, high salt spray, high vibration, and anti mold growth to ensure high availability.
Improve and optimize the attachment structure function, add multiple reliability tests, and enhance reliability.
VW3-25 ACB crafted for PV, wind, & storage systems. Features 3P/4P and Icu:50kA~85kA. Peak breaking capacity at 80KA within 800Vac. Robust against damp heat, salt mist & mixed gases. Stable at 5,000m altitude. Advanced remote capabilities
VW3-63 ACB, the choice for PV, wind, & storage. Equipped with 3P/4P & stellar Icu:50kA~135kA. Delivers 80KA break at 800Vac. Exceptional in withstanding humidity, temperature shifts, & saline conditions. Stable up to 5,000m. Eco-friendly with full remote capabilities.
Digital twin, Internet of Things, big data, artificial intelligence, industrial Internet and other technologies are applied to realize digital design, intelligent production, intelligent management, collaborative manufacturing, green low-carbon manufacturing, and security management.